IES RP-8-25 parking lot lighting requirements
The IES recommendation for all parking lots is a minimum of 0.2 fc (2 lux) on the pavement, with the maximum no more than 20 times the minimum, and a minimum vertical illuminance of 0.1 fc (1 lux) at 5 ft. That is ANSI/IES RP-8-25, Table 17-1, as corrected by its errata of February and April 2026, and it is the same as the previous edition, RP-8-18 with Addendum 1. The table as first printed in RP-8-25 showed these values as averages, with Max:Avg 4:1, plus rows for EV charging stations; the errata strike both. Local codes and ordinances can replace the IES values.
Correction, 2026-10-16: an earlier version of this page reported the table as first printed (0.2 fc average, Max:Avg 4:1) as the current recommendation. We had not applied RP-8-25 Errata 1 and 2. The values below are corrected.
The values
| Criterion | RP-8-25 with Errata 1 and 2 (same in RP-8-18+A1) | RP-8-25 as first printed, struck by the errata |
|---|---|---|
| All parking lots, horizontal, at grade | 0.2 fc (2 lux) minimum | 0.2 fc (2 lux) average |
| Horizontal uniformity | Max:Min 20:1 or less | Max:Avg 4:1 or less |
| All parking lots, vertical, at 5 ft | 0.1 fc (1 lux) minimum | 0.1 fc (1 lux) average |
| Vertical uniformity | Max:Min 20:1 or less | Max:Avg 20:1 or less |
| EV charging stations | No separate rows | 3 to 20 fc average by activity level and lighting zone |
| Transaction areas, before curfew | 0.9 fc (10 lux) minimum horizontal, 0.5 fc (5 lux) minimum vertical, Max:Min 15:1 (unchanged by the errata) | |
| Transaction areas, after curfew | 0.2 fc (2 lux) minimum horizontal, 0.1 fc (1 lux) minimum vertical, Max:Min 15:1 (unchanged) | |
| Pay machines, vertical on the front face | 2.8 fc (30 lux) before curfew, 1.4 fc (15 lux) after (unchanged) | |
The table covers parking lots and the top floor of parking garages, is titled as basic requirements and not for areas where security is an issue, and gives values to be maintained over time, so the design includes a light loss factor. The parking-lot rows apply to lighting zones LZ1 to LZ4 (table note 1).
How the standard says to calculate it
- Horizontal grid: the entire parking pavement, points no farther apart than one third of the mounting height, starting within half a grid spacing of the boundary (RP-8-25, 17.4.3.1).
- Vertical points: 5 ft above grade, at least on the drive-aisle centerline, spaced no more than one third of the mounting height, facing the directions of vehicle travel, each direction assessed separately (17.4.3.2).
- Not outward: vertical values are not required facing out along a boundary or beyond the outer line of luminaires (17.4.3.2).
- Maintained: the values are to be maintained over time (table note c), so calculations include a light loss factor.
A worked example
The 300 × 200 ft lot on our homepage: 8 poles of a 166 W Type III at 30 ft, light loss factor 0.9, horizontal points every 10 ft (one third of the mounting height), vertical points at 5 ft on the aisle centerline in both directions.
| Check | Result | RP-8-25 with errata |
|---|---|---|
| Horizontal, 651 points | min 0.25 · avg 2.20 · max 4.36 fc | min ≥ 0.2: yes |
| Horizontal uniformity | Max:Min 17.6 | ≤ 20: yes |
| Vertical, one direction | min 0.11 · max 1.39 fc | min ≥ 0.1, Max:Min 12.5: yes |
| Vertical, other direction | min 0.23 · max 4.17 fc | min ≥ 0.1, Max:Min 17.8: yes |
Runnax judges on exactly this form, a minimum and a Max:Min ratio. The hosted tool checks it on the poles you place, or searches for the fewest new poles that meet it inside the areas you allow and says whether every layout with fewer poles was tried; the research engine additionally searches regular pole arrays and keeps the fewest poles it found that pass, not a proven minimum. These are simulations, direct light only, and not a compliance statement. Pole counts for other lot sizes.
What the IES tables are not
- Not law. RP-8 is a recommended practice. Its table notes say codes, ordinances or mandates may supersede the values and that the designer makes the final determination of criteria.
- Not security lighting. The table is for basic requirements. For security, RP-8 points to IES G-1.
- Not OSHA. The often-quoted OSHA table (29 CFR 1926.56, Table D-3) covers construction areas while work is in progress and does not mention parking lots.
Questions
What are the IES foot-candle requirements for a parking lot?
IES RP-8-25 (Table 17-1, as corrected by Errata 1 and 2 in 2026) recommends, for all parking lots, a minimum of 0.2 fc (2 lux) on the pavement with a maximum-to-minimum ratio of 20:1 or less, and a minimum vertical illuminance of 0.1 fc (1 lux) at 5 ft with Max:Min 20:1 or less. Pedestrian and vehicle transaction areas have higher values: 0.9 fc minimum before curfew.
Is it 0.2 fc minimum or 0.2 fc average?
Minimum. The table as first printed in RP-8-25 showed 0.2 fc as an average with Max:Avg 4:1. Errata 1 (February 15, 2026) and Errata 2 (April 17, 2026) correct it to 0.2 fc minimum with Max:Min 20:1, the same as RP-8-18 with Addendum 1. If your copy has no errata applied, it shows the uncorrected values.
Are the IES values a legal requirement?
No. RP-8 is a recommended practice. Its own table notes say codes, ordinances or mandates may supersede the values and that the designer makes the final determination of criteria. Check the code and permit rules where the lot is.
Does OSHA set parking lot lighting levels?
The OSHA illumination table that is often quoted, 29 CFR 1926.56 Table D-3, applies to construction areas while work is in progress. It does not mention parking lots.
Does RP-8-25 give values for EV charging stations?
Not any more. The table as first printed had EV charging rows with average targets by activity level and lighting zone; Errata 1 and 2 strike those rows.
Where is vertical illuminance measured?
At 5 ft above finished grade, at least on the drive-aisle centerline, in the primary directions of vehicle travel, with each direction assessed separately (RP-8-25, Section 17.4.3.2).
Can Runnax check my lot against these values?
The hosted tool at sim.runnax.com checks the horizontal values against the requirement you enter, on every grid point of every area: on the poles you place, or while it searches for the fewest new poles inside the areas you allow, and says whether every layout with fewer poles was tried. On given poles it can also check vertical targets you enter. These are simulations, not a compliance statement.
Sources
- ANSI/IES RP-8-25, Recommended Practice: Lighting Roadway and Parking Facilities, Part 2, Chapter 17, Table 17-1 (page 17-10), and Sections 17.4.3.1 and 17.4.3.2. Illuminating Engineering Society, 2025.
- ANSI/IES RP-8-25 Errata 1, February 15, 2026 and ANSI/IES RP-8-25 Errata 2, April 17, 2026: the parking lot illuminance table correction. Illuminating Engineering Society.
- ANSI/IES RP-8-18+A1, Design and Maintenance of Roadway and Parking Facility Lighting, Chapter 17, Table 17-2. Illuminating Engineering Society.
- 29 CFR 1926.56, Illumination, osha.gov.
Values are quoted from the published documents for reference. Your specification, code or authority having jurisdiction decides which edition and which values apply.