IES RP-8-25 parking lot lighting requirements

Last updated 2026-11-05 · every value cites its table · checked against the published documents and errata

The IES recommendation for all parking lots is a minimum of 0.2 fc (2 lux) on the pavement, with the maximum no more than 20 times the minimum, and a minimum vertical illuminance of 0.1 fc (1 lux) at 5 ft. That is ANSI/IES RP-8-25, Table 17-1, as corrected by its errata of February and April 2026, and it is the same as the previous edition, RP-8-18 with Addendum 1. The table as first printed in RP-8-25 showed these values as averages, with Max:Avg 4:1, plus rows for EV charging stations; the errata strike both. Local codes and ordinances can replace the IES values.

Correction, 2026-10-16: an earlier version of this page reported the table as first printed (0.2 fc average, Max:Avg 4:1) as the current recommendation. We had not applied RP-8-25 Errata 1 and 2. The values below are corrected.

The values

CriterionRP-8-25 with Errata 1 and 2 (same in RP-8-18+A1)RP-8-25 as first printed, struck by the errata
All parking lots, horizontal, at grade0.2 fc (2 lux) minimum0.2 fc (2 lux) average
Horizontal uniformityMax:Min 20:1 or lessMax:Avg 4:1 or less
All parking lots, vertical, at 5 ft0.1 fc (1 lux) minimum0.1 fc (1 lux) average
Vertical uniformityMax:Min 20:1 or lessMax:Avg 20:1 or less
EV charging stationsNo separate rows3 to 20 fc average by activity level and lighting zone
Transaction areas, before curfew0.9 fc (10 lux) minimum horizontal, 0.5 fc (5 lux) minimum vertical, Max:Min 15:1 (unchanged by the errata)
Transaction areas, after curfew0.2 fc (2 lux) minimum horizontal, 0.1 fc (1 lux) minimum vertical, Max:Min 15:1 (unchanged)
Pay machines, vertical on the front face2.8 fc (30 lux) before curfew, 1.4 fc (15 lux) after (unchanged)

The table covers parking lots and the top floor of parking garages, is titled as basic requirements and not for areas where security is an issue, and gives values to be maintained over time, so the design includes a light loss factor. The parking-lot rows apply to lighting zones LZ1 to LZ4 (table note 1).

Check your own lot against these values. Upload a site plan image, enter 0.2 fc minimum and 20:1 Max:Min (or your local code's values), and the hosted tool calculates every grid point. On existing poles it picks the fixture and aiming that meet them, or tells you none does; for a new lot it searches for the fewest new poles that meet them, and says whether every layout with fewer poles was tried. Vertical targets can be checked on given poles. You need a PNG or JPEG site plan with three lines of known length (one sets the scale, one horizontal and one vertical check it) (what image works). Free trial: 30 calculations per company, no credit card.

Start free trial

How the standard says to calculate it

A worked example

The 300 × 200 ft lot on our homepage: 8 poles of a 166 W Type III at 30 ft, light loss factor 0.9, horizontal points every 10 ft (one third of the mounting height), vertical points at 5 ft on the aisle centerline in both directions.

CheckResultRP-8-25 with errata
Horizontal, 651 pointsmin 0.25 · avg 2.20 · max 4.36 fcmin ≥ 0.2: yes
Horizontal uniformityMax:Min 17.6≤ 20: yes
Vertical, one directionmin 0.11 · max 1.39 fcmin ≥ 0.1, Max:Min 12.5: yes
Vertical, other directionmin 0.23 · max 4.17 fcmin ≥ 0.1, Max:Min 17.8: yes

Runnax judges on exactly this form, a minimum and a Max:Min ratio. The hosted tool checks it on the poles you place, or searches for the fewest new poles that meet it inside the areas you allow and says whether every layout with fewer poles was tried; the research engine additionally searches regular pole arrays and keeps the fewest poles it found that pass, not a proven minimum. These are simulations, direct light only, and not a compliance statement. Pole counts for other lot sizes.

What the IES tables are not

Questions

What are the IES foot-candle requirements for a parking lot?

IES RP-8-25 (Table 17-1, as corrected by Errata 1 and 2 in 2026) recommends, for all parking lots, a minimum of 0.2 fc (2 lux) on the pavement with a maximum-to-minimum ratio of 20:1 or less, and a minimum vertical illuminance of 0.1 fc (1 lux) at 5 ft with Max:Min 20:1 or less. Pedestrian and vehicle transaction areas have higher values: 0.9 fc minimum before curfew.

Is it 0.2 fc minimum or 0.2 fc average?

Minimum. The table as first printed in RP-8-25 showed 0.2 fc as an average with Max:Avg 4:1. Errata 1 (February 15, 2026) and Errata 2 (April 17, 2026) correct it to 0.2 fc minimum with Max:Min 20:1, the same as RP-8-18 with Addendum 1. If your copy has no errata applied, it shows the uncorrected values.

Are the IES values a legal requirement?

No. RP-8 is a recommended practice. Its own table notes say codes, ordinances or mandates may supersede the values and that the designer makes the final determination of criteria. Check the code and permit rules where the lot is.

Does OSHA set parking lot lighting levels?

The OSHA illumination table that is often quoted, 29 CFR 1926.56 Table D-3, applies to construction areas while work is in progress. It does not mention parking lots.

Does RP-8-25 give values for EV charging stations?

Not any more. The table as first printed had EV charging rows with average targets by activity level and lighting zone; Errata 1 and 2 strike those rows.

Where is vertical illuminance measured?

At 5 ft above finished grade, at least on the drive-aisle centerline, in the primary directions of vehicle travel, with each direction assessed separately (RP-8-25, Section 17.4.3.2).

Can Runnax check my lot against these values?

The hosted tool at sim.runnax.com checks the horizontal values against the requirement you enter, on every grid point of every area: on the poles you place, or while it searches for the fewest new poles inside the areas you allow, and says whether every layout with fewer poles was tried. On given poles it can also check vertical targets you enter. These are simulations, not a compliance statement.

Sources

Values are quoted from the published documents for reference. Your specification, code or authority having jurisdiction decides which edition and which values apply.

Check these values on your lot: Start free trial