How it's verified
Runnax computes illuminance with the point method, the same formula IES RP-8 uses: E = I(γ, C) · cos θ / d² · LLF, summed over every luminaire head. We check it against the tools engineers already trust, on real projects, and we publish where it falls short.
Point by point on given poles, against AGi32
On given poles, the hosted tool (sim.runnax.com) computes illuminance and picks luminaire and aiming among the candidates you choose; it also searches new pole layouts inside the areas you allow (results below). Our calculation was compared with AGi32 on a real parking-lot project from our archive, with given poles: 473 of 473 grid points agree, largest difference 0.13 % (horizontal illuminance, direct light, same IES file and light loss factor). This comparison ran in the research version of the engine and has not yet been repeated in the hosted tool. Reported, not independently reviewed. The first run failed (37–42 % off in three areas) because the luminaire insertion point was taken as the photometric centre; with the 1 m arm offset entered, all 473 points agreed. In the hosted tool, place each luminaire at its photometric centre (arm offset included).
- Not passed: a tilt-angle comparison failed on one case; the root cause was traced to how AGi32 samples a node directly above the luminaire. The sign convention of the tilt was then checked against AGi32 on one case (2026-10-31: one PLB150 photometric file, 25 ft, orientation 90° only, tilt +10°/−10°/0°, horizontal grid; all 49 points within tolerance in each of the three runs). Other photometric files, other orientation/tilt combinations, vertical planes and the physical installation direction were not covered by that check.
- Reported, not independently reviewed: vertical-plane illuminance (released engine code, run offline): two cases of 40 points each (four luminaires; the second with mixed orientations and tilts +5°/−5°/+10°/0°), 40 of 40 within tolerance in each, largest difference 1.22 %; one oblique line of 62 points, worst 0.97 %.
- Reported, not independently reviewed: property-line light (a hosted-tool job on the test station): 20 sample points on four boundary segments (same IES, four luminaires, direct light), 20 of 20 within tolerance, largest difference 1.73 % at two low-illuminance midpoints; it shows that both tools calculate the same thing at these points, not that the property line is within any limit.
- Reported, not independently reviewed: LCS zonal lumens (method checked against AGi32 before implementation; the product engine reproduces those values in its tests): three luminaires, ten zones each, all within tolerance, largest difference 1.4 lm.
- Reported, not independently reviewed: layout search (synthetic acceptance site): on a synthetic new lot with one demo luminaire it tried 26,577 layouts and kept 3 new poles, after every layout with fewer poles had been tried; the top three were rechecked with a full calculation. There is no AGi32 comparison of a layout yet and no real site yet.
- Tolerance for these comparisons: relative difference ≤ 2 % where AGi32 reads ≥ 0.1 fc, otherwise ≤ 0.002 fc; zonal lumens ≤ max(1 %, 2 lm). These are our own acceptance criteria, not an RP-8 or AGi32 standard.
- Not validated in production use: the optional RP-8-25 Table 17-1 reference reading; multi-user load.
Research engine (Runnax Engine) — not the hosted tool
The sections below belong to the research engine that searches pole layouts. They are published as research results and are not claims about the hosted tool.
Parking: a real lot, point by point
A municipal sports-complex parking lot in South Dakota: 15 heads of a 75 W, 13,000 lm luminaire at 25 ft, 271 points on a 20 ft grid, light loss factor 1.0. We compared the engine with an AGi32 direct-light run of the same lot.
| Engine | AGi32, direct light | |
|---|---|---|
| Minimum | 0.3949 fc | 0.3946 fc |
| Average | 1.2367 fc | 1.2366 fc |
| Maximum | 4.7935 fc | 4.7930 fc |
| Avg:Min | 3.1312 | 3.1337 |
The design actually delivered to that customer averaged 1.2159 fc with Avg:Min 3.1998, so the engine reads 1.7 % higher on average than the delivered file. Both pass the customer's criteria. The project's 25-test acceptance suite passes 25 of 25, last run 2026-10-08. Read the case.
Recomputing an AGi32 file (research tool; intake currently paused)
Runnax also recomputes an existing AGi32 (.AGI) file from the data inside it: luminaire positions and aiming, the photometric data AGi32 used, light loss factors and every calculation point. On three real parking-lot files, each recomputed in about 4 seconds:
| File | Heads | Calculation zones | Largest zone-average difference |
|---|---|---|---|
| Parking lot A | 48 | 2 horizontal, 2 vertical | 0.06 % |
| Parking lot B (the case above) | 15 | 1 horizontal, 2 vertical | 0.03 % |
| Parking lot C (metric) | 40 | 3 horizontal, 1 vertical | 0.01 % |
Each recomputation also reports what the file assumes; for example, a light loss factor of 1.0 is flagged because it applies no lamp or dirt depreciation. Project names are withheld.
Roadway: area averages on real projects (2023 roadway study, EN 13201 — not the parking product)
| Reference tool | Zones | Difference in average illuminance |
|---|---|---|
| AGi32, project A | 3 | −0.62 %, −0.65 %, −3.61 % |
| AGi32, project B | 3 | +0.26 %, +0.69 %, −3.06 % |
| DIALux, 2 projects (2023 roadway study) | 3 | −0.30 %, +0.12 %, −0.07 % |
Largest difference across all 9 zones: 3.61 %. Sidewalk zones agree within 0.69 %; the roadway zones read 3.06 % to 3.61 % low against AGi32, and we have not found the cause yet. Of the arrangements, only single-side poles have reached project-level validation.
Known deviations (research engine)
- Roadway point values: on two 510-point comparisons with AGi32, median differences were 4.27 % and 4.47 %, and the worst points were 36.68 % and 40.83 %. We don't quote roadway point values on their own.
- Roadway minimum and uniformity: minimums differ by 8.47–15.48 % and Avg:Min by up to 22.71 % against AGi32. This is why the engine issues no roadway pass/fail yet.
- Opposite and median roadway arrangements calculate but have no independent validation; staggered is blocked.
The homepage demo (research engine)
The lot on the homepage is synthetic: 300 × 200 ft, drawn before the run, with poles allowed only on the islands and curbs. The engine tried 24,904 layouts in 64 s and kept 8 poles of a 166 W Type III luminaire (measured IES) at 30 ft: minimum 0.25 fc, Max:Min 17.6 on 651 points, vertical minimum 0.11 fc. The in-browser sandbox uses the same IES table and point method and reproduces the engine's 651 values exactly.
What we don't claim
- No RP-8 or code-compliance statements. The tool compares results with the targets you set; the optional RP-8-25 Table 17-1 reference reading is not a compliance statement.
- No claim that the hosted tool is verified against AGi32: the property-line comparison ran in it (test station); the 473-point comparison has not been repeated in it. Tilt-angle agreement failed on one case, and the 473-point, vertical, property-line and zonal-lumen results are reported, not independently reviewed.
- No claim that the research engine's regular-array search is the hosted tool's layout search, and no claim that a layout is the fewest possible unless the result says every layout with fewer poles was tried.
- No field verification yet: nothing has been compared with measured light levels.
- No inter-reflection, obstructions or shadowing: direct light only.